NPS 24 Pipe Dimensions
Outside diameter 24.000 in (609.6 mm) — fixed across every schedule. 13 wall thicknesses from ASME B36.10, with bore, weight, flow and pressure capacity for each, and the flanges and fittings that go with the size.
- Nominal size
- NPS 24
- Metric designator
- DN 600
- Outside diameter
- 24.000 in (609.6 mm)
- Schedules listed
- 13
- Standard weight wall
- 0.375 in (9.5 mm)
- Extra strong wall
- 0.500 in (12.7 mm)
What NPS 24 is
NPS 24 pipe measures 24.000 in (609.6 mm) across the outside, so here the size designation and the outside diameter in inches are the same number. That holds from NPS 14 upward and for no size below it. The metric designator is DN 600, which is likewise a label and not a measurement in millimetres. Whatever the schedule, the outside diameter stays at 24.000 in (609.6 mm): a heavier wall grows inward and takes the difference out of the bore.
The largest size covered by ASME B16.5 flanges and by the B16.9 tables on this site. Used for cooling water mains, flare headers and large transfer lines.
Every schedule in NPS 24
Dimensions are given in inches, with the millimetre equivalent beneath in grey.
| Schedule | Wall thickness | Inside diameter | Weight, empty | Weight, water filled | Flow area (in²) | Water (US gal/ft) |
|---|---|---|---|---|---|---|
| Sch 5 | 0.2185.54 mm | 23.564598.53 mm | 55.4282.48 kg/m | 244.48363.83 kg/m | 436.10 | 22.655 |
| Sch 10 | 0.2506.35 mm | 23.500596.90 mm | 63.4794.46 kg/m | 251.51374.28 kg/m | 433.74 | 22.532 |
| Sch 20 | 0.3759.52 mm | 23.250590.55 mm | 94.71140.94 kg/m | 278.76414.84 kg/m | 424.56 | 22.055 |
| Sch 30 | 0.56214.27 mm | 22.876581.05 mm | 140.81209.55 kg/m | 318.99474.71 kg/m | 411.01 | 21.351 |
| Sch 40 | 0.68817.48 mm | 22.624574.65 mm | 171.45255.15 kg/m | 345.73514.50 kg/m | 402.00 | 20.883 |
| STD | 0.3759.52 mm | 23.250590.55 mm | 94.71140.94 kg/m | 278.76414.84 kg/m | 424.56 | 22.055 |
| Sch 60 | 0.96924.61 mm | 22.062560.37 mm | 238.57355.03 kg/m | 404.30601.66 kg/m | 382.28 | 19.859 |
| Sch 80 | 1.21930.96 mm | 21.562547.67 mm | 296.86441.78 kg/m | 455.16677.36 kg/m | 365.15 | 18.969 |
| XS | 0.50012.70 mm | 23.000584.20 mm | 125.61186.92 kg/m | 305.73454.97 kg/m | 415.48 | 21.583 |
| Sch 100 | 1.53138.89 mm | 20.938531.83 mm | 367.74547.25 kg/m | 517.01769.39 kg/m | 344.32 | 17.887 |
| Sch 120 | 1.81246.02 mm | 20.376517.55 mm | 429.79639.59 kg/m | 571.15849.97 kg/m | 326.08 | 16.939 |
| Sch 140 | 2.06252.37 mm | 19.876504.85 mm | 483.57719.64 kg/m | 618.09919.81 kg/m | 310.28 | 16.118 |
| Sch 160 | 2.34459.54 mm | 19.312490.52 mm | 542.64807.54 kg/m | 669.63996.52 kg/m | 292.92 | 15.216 |
Inside diameter is OD − 2t. Weight is calculated for carbon steel as w = 10.69 × t × (OD − t) lb/ft and is the plain-end weight, excluding coatings, linings and fittings. Water-filled weight adds fresh water at 8.3454 lb per US gallon.
Reading the table
B36.10 lists 13 designations in NPS 24, which between them give 12 different wall thicknesses. The lightest is Schedule 5 at 0.218 in (5.5 mm) and the heaviest is Schedule 160 at 2.344 in (59.5 mm). Going from one to the other takes the bore from 23.564 in (598.5 mm) down to 19.312 in (490.5 mm), which cuts the flow area by 33% and raises the weight from 55.42 to 542.64 lb/ft, a factor of 9.8.
Standard weight equals Schedule 20 in this size. Extra strong does not coincide with a numbered schedule here. Where two designations share a wall they are the same pipe under two names, and either may appear on a mill certificate. The match is specific to the size, so it is the wall thickness in inches that should go on a requisition, not the designation alone.
For handling and support loads, a 20 ft length of standard weight NPS 24 pipe weighs about 1894 lb (859 kg) empty and 5575 lb (2529 kg) full of water. The water-filled figure is the one that governs pipe support spacing and the load during a hydrostatic test, including on lines that will carry gas or vapour in service.
Flow and pressure capacity by schedule
Two questions decide a schedule: how much the bore will carry, and how much pressure the wall will hold. The flow columns give the water flow through each bore at three velocities that bracket ordinary liquid service, from a pump suction line at the low end to a pump discharge line at the high end. The pressure columns are the ASME B31.3 pressure design equation solved for pressure, first on the nominal wall and then on the wall after the 12.5% mill under-tolerance that seamless pipe is allowed.
| Schedule | Flow at 3 ft/s (US gpm) | Flow at 6 ft/s (US gpm) | Flow at 10 ft/s (US gpm) | Pressure, nominal wall | Pressure, wall less 12.5% |
|---|---|---|---|---|---|
| Sch 5 | 4,077.8 | 8,155.7 | 13,592.8 | 366 psig | 320 psig |
| Sch 10 | 4,055.7 | 8,111.4 | 13,519.0 | 420 psig | 367 psig |
| Sch 20 | 3,969.9 | 7,939.8 | 13,232.9 | 633 psig | 553 psig |
| Sch 30 | 3,843.2 | 7,686.4 | 12,810.6 | 955 psig | 833 psig |
| Sch 40 | 3,759.0 | 7,518.0 | 12,529.9 | 1,174 psig | 1,024 psig |
| STD | 3,969.9 | 7,939.8 | 13,232.9 | 633 psig | 553 psig |
| Sch 60 | 3,574.6 | 7,149.1 | 11,915.2 | 1,669 psig | 1,454 psig |
| Sch 80 | 3,414.4 | 6,828.7 | 11,381.2 | 2,118 psig | 1,843 psig |
| XS | 3,885.0 | 7,769.9 | 12,949.9 | 847 psig | 740 psig |
| Sch 100 | 3,219.6 | 6,439.2 | 10,732.0 | 2,689 psig | 2,337 psig |
| Sch 120 | 3,049.1 | 6,098.2 | 10,163.6 | 3,214 psig | 2,790 psig |
| Sch 140 | 2,901.3 | 5,802.6 | 9,670.9 | 3,690 psig | 3,200 psig |
| Sch 160 | 2,739.0 | 5,477.9 | 9,129.9 | 4,238 psig | 3,669 psig |
Flow is velocity × flow area. Pressure is P = 2·S·t / (D − 2·Y·t) with S = 20,000 psi, E = W = 1.0 and Y = 0.4: seamless carbon steel such as A106 Gr B at moderate temperature, with no corrosion allowance and no threading allowance. It is an illustration of the arithmetic, not a design rating.
The method behind both halves of that table is set out in the pipe sizing guide and the wall thickness guide, each with a worked example.
Flanges for NPS 24 pipe
ASME B16.5 sizes a flange from the NPS and the pressure class, never from the schedule, so every flange below fits every wall in the table above. In NPS 24 a Class 150 flange is 32.00 in (812.8 mm) across and 1.81 in (46.0 mm) thick, held by 20 bolts of 1 1/4 in. A Class 1500 flange for the same pipe is 46.00 in (1168.4 mm) across and 8.00 in (203.2 mm) thick, on 16 bolts of 3 1/2 in. Because the bolt circle moves with the class, flanges of two different classes will not bolt together even though both fit the pipe.
| Class | Flange OD | Thickness | Bolt circle | Bolting | Raised face OD | Rating @ 100 °F |
|---|---|---|---|---|---|---|
| Class 150 | 32.00812.80 mm | 1.8145.97 mm | 29.50749.30 mm | 20 × 1 1/4 in | 27.25692.15 mm | 285 psig |
| Class 300 | 36.00914.40 mm | 2.6968.33 mm | 32.00812.80 mm | 24 × 1 1/2 in | 27.25692.15 mm | 740 psig |
| Class 400 | 36.00914.40 mm | 3.0076.20 mm | 32.00812.80 mm | 24 × 1 3/4 in | 27.25692.15 mm | 985 psig |
| Class 600 | 37.00939.80 mm | 4.00101.60 mm | 33.00838.20 mm | 24 × 1 7/8 in | 27.25692.15 mm | 1480 psig |
| Class 900 | 41.001041.40 mm | 5.50139.70 mm | 35.50901.70 mm | 20 × 2 1/2 in | 27.25692.15 mm | 2220 psig |
| Class 1500 | 46.001168.40 mm | 8.00203.20 mm | 39.00990.60 mm | 16 × 3 1/2 in | 27.25692.15 mm | 3705 psig |
Ratings are for A105 carbon steel at 100 °F and fall with temperature. Thickness excludes the raised face. All six flange types share these dimensions.
The one flange dimension that does follow the schedule is the bore of a weld neck flange, which is machined to the inside diameter of the pipe it is welded to. A weld neck flange for standard weight NPS 24 pipe is bored 23.250 in (590.5 mm); ordered for Schedule 160 it is bored 19.312 in (490.5 mm). The schedule therefore belongs on every weld neck flange requisition.
| Class | Weld neck | Slip-on / threaded | Lap joint | Raised face height |
|---|---|---|---|---|
| Class 150 | 5.94150.88 mm | 3.1981.03 mm | 4.38111.25 mm | 0.06 in (1.5 mm) |
| Class 300 | 6.56166.62 mm | 4.12104.65 mm | 6.00152.40 mm | 0.06 in (1.5 mm) |
Length through hub is how far the flange stands off the joint, which is what a spool drawing needs. It is measured from the flange face, without the raised face, and is tabulated here for Classes 150 and 300.
Buttweld fittings for NPS 24 pipe
ASME B16.9 sets the dimensions of a buttweld fitting from the NPS alone, so the figures below hold for every schedule in the size. A long radius 90° elbow in NPS 24 measures 36.00 in (914.4 mm) from its centre to each end, which is the figure a piping layout adds for every change of direction. The fitting is still ordered to a schedule, because its wall has to match the pipe at the weld.
| Fitting | Dimension | NPS 24 |
|---|---|---|
| 90° Long Radius Elbow | Centre-to-end A | 36.00914.40 mm |
| 90° Short Radius Elbow | Centre-to-end A | 24.00609.60 mm |
| 45° Long Radius Elbow | Centre-to-end B | 15.00381.00 mm |
| 180° Long Radius Return Bend | Centre-to-centre O | 72.001828.80 mm |
| Straight Tee | Centre-to-end C and M | 17.00431.80 mm |
| Reducing Tee | Run centre-to-end C | 17.00431.80 mm |
| Straight Cross | Centre-to-end C | 17.00431.80 mm |
| Concentric Reducer | End-to-end H | 20.00508.00 mm |
| Eccentric Reducer | End-to-end H | 20.00508.00 mm |
| Cap | Length E | 10.50266.70 mm |
The cap is the exception to the rule above: its length is for walls up to a limiting thickness, and a heavier wall takes a longer cap. See the cap page.
Guides and comparisons for this page
NPS 24 in each schedule chart
Common questions
What is the outside diameter of NPS 24 pipe?
NPS 24 pipe has an outside diameter of 24.000 in (609.6 mm). That outside diameter is fixed: it is identical in every schedule, and only the wall thickness — and therefore the bore — changes from one schedule to the next.
What is the inside diameter of NPS 24 schedule 40 pipe?
22.624 in (574.6 mm). The 0.688 in (17.5 mm) wall comes off the 24.000 in (609.6 mm) outside diameter twice, once on each side, which leaves that bore and a flow area of 402.00 in².
How much does NPS 24 schedule 40 pipe weigh?
171.45 lb/ft (255.15 kg/m) as plain-end carbon steel, on a wall thickness of 0.688 in (17.5 mm). It holds 20.883 US gallons of water per foot.
What is the metric equivalent of NPS 24?
DN 600. DN is a dimensionless designator, not a measurement — DN 600 pipe does not measure 600 mm anywhere. Its actual outside diameter is 609.6 mm.