NPS 4 Pipe Dimensions

Outside diameter 4.500 in (114.3 mm) — fixed across every schedule. 10 wall thicknesses from ASME B36.10, with bore, weight, flow and pressure capacity for each, and the flanges and fittings that go with the size.

Nominal size
NPS 4
Metric designator
DN 100
Outside diameter
4.500 in (114.3 mm)
Schedules listed
10
Standard weight wall
0.237 in (6.0 mm)
Extra strong wall
0.337 in (8.6 mm)

What NPS 4 is

NPS 4 pipe measures 4.500 in (114.3 mm) across the outside, which is 0.500 in more than the 4 in its name suggests. Below NPS 14 the designation is a label inherited from iron pipe sizing and matches neither the outside diameter nor the bore of any schedule exactly. The metric designator is DN 100, which is likewise a label and not a measurement in millimetres. Whatever the schedule, the outside diameter stays at 4.500 in (114.3 mm): a heavier wall grows inward and takes the difference out of the bore.

One of the most widely used sizes in process, utility and fire water service, and one of the best stocked in every schedule.

Pipe wall thickness to scale, NPS 4Pipe cross-sections drawn to scale at the same outside diameter so the wall thicknesses can be compared. Sch 5: 0.083 in wall · 4.334 in bore; STD: 0.237 in wall · 4.026 in bore; XXS: 0.674 in wall · 3.152 in boreSch 50.083 in wall · 4.334 in boreSTD0.237 in wall · 4.026 in boreXXS0.674 in wall · 3.152 in bore
NPS 4 pipe drawn to scale. Every section is 4.500 in (114.3 mm) across the outside. Only the wall changes, and the bore takes up the difference.

Every schedule in NPS 4

Dimensions are given in inches, with the millimetre equivalent beneath in grey.

ASME B36.10 wall thicknesses for NPS 4 (DN 100), outside diameter 4.500 in (114.3 mm).
ScheduleWall thicknessInside diameterWeight, emptyWeight, water filledFlow area (in²)Water (US gal/ft)
Sch 50.0832.11 mm4.334110.08 mm3.925.83 kg/m10.3115.35 kg/m14.750.766
Sch 100.1203.05 mm4.260108.20 mm5.628.36 kg/m11.8017.56 kg/m14.250.740
Sch 300.1884.78 mm4.124104.75 mm8.6712.90 kg/m14.4621.51 kg/m13.360.694
Sch 400.2376.02 mm4.026102.26 mm10.8016.07 kg/m16.3224.29 kg/m12.730.661
STD0.2376.02 mm4.026102.26 mm10.8016.07 kg/m16.3224.29 kg/m12.730.661
Sch 800.3378.56 mm3.82697.18 mm15.0022.32 kg/m19.9829.74 kg/m11.500.597
XS0.3378.56 mm3.82697.18 mm15.0022.32 kg/m19.9829.74 kg/m11.500.597
Sch 1200.43811.13 mm3.62492.05 mm19.0228.30 kg/m23.4934.96 kg/m10.310.536
Sch 1600.53113.49 mm3.43887.33 mm22.5333.53 kg/m26.5539.52 kg/m9.280.482
XXS0.67417.12 mm3.15280.06 mm27.5741.02 kg/m30.9546.06 kg/m7.800.405

Inside diameter is OD − 2t. Weight is calculated for carbon steel as w = 10.69 × t × (OD − t) lb/ft and is the plain-end weight, excluding coatings, linings and fittings. Water-filled weight adds fresh water at 8.3454 lb per US gallon.

Reading the table

B36.10 lists 10 designations in NPS 4, which between them give 8 different wall thicknesses. The lightest is Schedule 5 at 0.083 in (2.1 mm) and the heaviest is Double Extra Strong (XXS) at 0.674 in (17.1 mm). Going from one to the other takes the bore from 4.334 in (110.1 mm) down to 3.152 in (80.1 mm), which cuts the flow area by 47% and raises the weight from 3.92 to 27.57 lb/ft, a factor of 7.0.

Standard weight equals Schedule 40 in this size. Extra strong equals Schedule 80. Where two designations share a wall they are the same pipe under two names, and either may appear on a mill certificate. The match is specific to the size, so it is the wall thickness in inches that should go on a requisition, not the designation alone.

For handling and support loads, a 20 ft length of standard weight NPS 4 pipe weighs about 216 lb (98 kg) empty and 326 lb (148 kg) full of water. The water-filled figure is the one that governs pipe support spacing and the load during a hydrostatic test, including on lines that will carry gas or vapour in service.

Flow and pressure capacity by schedule

Two questions decide a schedule: how much the bore will carry, and how much pressure the wall will hold. The flow columns give the water flow through each bore at three velocities that bracket ordinary liquid service, from a pump suction line at the low end to a pump discharge line at the high end. The pressure columns are the ASME B31.3 pressure design equation solved for pressure, first on the nominal wall and then on the wall after the 12.5% mill under-tolerance that seamless pipe is allowed.

Water flow and internal pressure capacity of NPS 4 pipe by schedule.
ScheduleFlow at 3 ft/s (US gpm)Flow at 6 ft/s (US gpm)Flow at 10 ft/s (US gpm)Pressure, nominal wallPressure, wall less 12.5%
Sch 5137.9275.9459.8749 psig654 psig
Sch 10133.3266.6444.31,090 psig951 psig
Sch 30124.9249.8416.31,729 psig1,506 psig
Sch 40119.0238.1396.82,199 psig1,914 psig
STD119.0238.1396.82,199 psig1,914 psig
Sch 80107.5215.0358.33,186 psig2,766 psig
XS107.5215.0358.33,186 psig2,766 psig
Sch 12096.5192.9321.54,222 psig3,656 psig
Sch 16086.8173.6289.35,212 psig4,502 psig
XXS73.0145.9243.26,807 psig5,856 psig

Flow is velocity × flow area. Pressure is P = 2·S·t / (D − 2·Y·t) with S = 20,000 psi, E = W = 1.0 and Y = 0.4: seamless carbon steel such as A106 Gr B at moderate temperature, with no corrosion allowance and no threading allowance. It is an illustration of the arithmetic, not a design rating.

The method behind both halves of that table is set out in the pipe sizing guide and the wall thickness guide, each with a worked example.

Flanges for NPS 4 pipe

ASME B16.5 sizes a flange from the NPS and the pressure class, never from the schedule, so every flange below fits every wall in the table above. In NPS 4 a Class 150 flange is 9.00 in (228.6 mm) across and 0.88 in (22.4 mm) thick, held by 8 bolts of 5/8 in. A Class 2500 flange for the same pipe is 14.00 in (355.6 mm) across and 3.00 in (76.2 mm) thick, on 8 bolts of 1 1/2 in. Because the bolt circle moves with the class, flanges of two different classes will not bolt together even though both fit the pipe.

ASME B16.5 flange dimensions in NPS 4, all published pressure classes.
ClassFlange ODThicknessBolt circleBoltingRaised face ODRating @ 100 °F
Class 1509.00228.60 mm0.8822.35 mm7.50190.50 mm8 × 5/8 in6.19157.23 mm285 psig
Class 30010.00254.00 mm1.1930.23 mm7.88200.15 mm8 × 3/4 in6.19157.23 mm740 psig
Class 40010.00254.00 mm1.3835.05 mm7.88200.15 mm8 × 7/8 in6.19157.23 mm985 psig
Class 60010.75273.05 mm1.5038.10 mm8.50215.90 mm8 × 7/8 in6.19157.23 mm1480 psig
Class 90011.50292.10 mm1.7544.45 mm9.25234.95 mm8 × 1 1/8 in6.19157.23 mm2220 psig
Class 150012.25311.15 mm2.1253.85 mm9.50241.30 mm8 × 1 1/4 in6.19157.23 mm3705 psig
Class 250014.00355.60 mm3.0076.20 mm10.75273.05 mm8 × 1 1/2 in6.19157.23 mm6170 psig

Ratings are for A105 carbon steel at 100 °F and fall with temperature. Thickness excludes the raised face. All six flange types share these dimensions.

The one flange dimension that does follow the schedule is the bore of a weld neck flange, which is machined to the inside diameter of the pipe it is welded to. A weld neck flange for standard weight NPS 4 pipe is bored 4.026 in (102.3 mm); ordered for Double Extra Strong (XXS) it is bored 3.152 in (80.1 mm). The schedule therefore belongs on every weld neck flange requisition.

ASME B16.5 length through hub, NPS 4.
ClassWeld neckSlip-on / threadedLap jointRaised face height
Class 1502.9474.68 mm1.2531.75 mm1.3133.27 mm0.06 in (1.5 mm)
Class 3003.3184.07 mm1.8145.97 mm1.8847.75 mm0.06 in (1.5 mm)

Length through hub is how far the flange stands off the joint, which is what a spool drawing needs. It is measured from the flange face, without the raised face, and is tabulated here for Classes 150 and 300.

Buttweld fittings for NPS 4 pipe

ASME B16.9 sets the dimensions of a buttweld fitting from the NPS alone, so the figures below hold for every schedule in the size. A long radius 90° elbow in NPS 4 measures 6.00 in (152.4 mm) from its centre to each end, which is the figure a piping layout adds for every change of direction. The fitting is still ordered to a schedule, because its wall has to match the pipe at the weld.

ASME B16.9 buttweld fitting dimensions in NPS 4.
FittingDimensionNPS 4
90° Long Radius ElbowCentre-to-end A6.00152.40 mm
90° Short Radius ElbowCentre-to-end A4.00101.60 mm
45° Long Radius ElbowCentre-to-end B2.5063.50 mm
180° Long Radius Return BendCentre-to-centre O12.00304.80 mm
Straight TeeCentre-to-end C and M4.12104.65 mm
Reducing TeeRun centre-to-end C4.12104.65 mm
Straight CrossCentre-to-end C4.12104.65 mm
Concentric ReducerEnd-to-end H4.00101.60 mm
Eccentric ReducerEnd-to-end H4.00101.60 mm
CapLength E2.5063.50 mm

The cap is the exception to the rule above: its length is for walls up to a limiting thickness, and a heavier wall takes a longer cap. See the cap page.

Guides and comparisons for this page

NPS 4 in each schedule chart

Common questions

What is the outside diameter of NPS 4 pipe?

NPS 4 pipe has an outside diameter of 4.500 in (114.3 mm). That outside diameter is fixed: it is identical in every schedule, and only the wall thickness — and therefore the bore — changes from one schedule to the next.

What is the inside diameter of NPS 4 schedule 40 pipe?

4.026 in (102.3 mm). The 0.237 in (6.0 mm) wall comes off the 4.500 in (114.3 mm) outside diameter twice, once on each side, which leaves that bore and a flow area of 12.73 in².

How much does NPS 4 schedule 40 pipe weigh?

10.80 lb/ft (16.07 kg/m) as plain-end carbon steel, on a wall thickness of 0.237 in (6.0 mm). It holds 0.661 US gallons of water per foot.

What is the metric equivalent of NPS 4?

DN 100. DN is a dimensionless designator, not a measurement — DN 100 pipe does not measure 100 mm anywhere. Its actual outside diameter is 114.3 mm.

Adjacent sizes